Water Sampling Station DCM 01
Water Values – Valuable Water
The DCM 01 has been especially developed for public swimming pools. Through the combination of a potentiostatic and a membrane covered measuring cell for measuring of free chlorine and the total chlorine with the powerful multi-channel controller TOPAX DX, an extensive measuring, display and control of all important parameters for the disinfection is now possible.
Water Sampling Station DCM 01
- For public swimming pools
- Potentiostatic measurement of free chlorine
- Membrane covered measuring cell for combined chlorine
- Measurement of pH value, Redox and temperature
- Powerful multi-channel controller TOPAX DX
- Flow monitoring
- Hydrostatic flow regulation
- Serial interface for PC communication (optional)
- Control of flocculants dosage (optional)
Further product views
Measuring range free chlorine | mg/l | up to 2, pH balanced | |
---|---|---|---|
Measuring range pH (optional) | 0...14 | ||
Measuring range redox (optional) | mV | 0...1000 | |
Dimensions (W x H x D) | mm | 490 x 900 x ~130 | |
Temperature | °C | 5...60 | |
Sample water requirement | l/h | approx. 45 | |
Water pressure input | bar | 0.2...6.0 | |
Water pressure ouput | outflow sample water must be able to run off | ||
Hydraulic connections input | mm | hose liner Ø6 Male | |
Hydraulic connections output | mm | hose liner Ø10 Male |